qiao@hvtest.cc15871365102

    < >

    UHVIW Series GIS No Partial Discharge Fault Simulation Test Device

    The instrument can be installed and tested under the running state of the equipment.High speed AD conversion circuit is used to digitize the signal.The reliability of detection data is guaranteed by digital signal processing, adaptive filtering and other interference signal processing methods.

    Product Details of UHVIW Series GIS No Partial Discharge Fault Simulation Test Device

    81db29d848f3d7e30f59fad76848a60c

    Product parameters:

    Used for on-line detection and localization of partial discharge in high voltage equipment

    2f67ea541048411ce2e4ef66a7a85352


    Technical parameters:

    High voltage no partial discharge transformer

    Rated voltage

    100kV

    Rated capacity

    5kVA

    Input voltage

    220V

    Input current

    22.7A

    High-voltage current

    0.05A

    Partial discharge capacity at rated voltage

    ≤ 3PC (overall system assessment)


    Coupling capacitor

    Rated voltage

    100KV

    Rated capacitance

    100pf

    Local discharge capacity at rated voltage

    ≤3PC

    Discharge model

    The discharge model is configured with particle discharge


    Feature:

    1. The device is small in size and has the smallest available space

    2. The components are lightweight

    3. It has a sturdy and durable structure that can withstand long-distance transportation

    4. Various tests can be completed in an unshielded testing environment

    5. All high-voltage parts are enclosed in a sealed space to ensure the high safety of the testing personnel

    6. For a wide range of applications, installing a sleeve can perform pressure tests on conventional equipment

    7. Built in high-voltage measuring and partial discharge coupling capacitors

    8. The partial discharge of the entire equipment is less than 3pC, ensuring the accuracy of the test data


    working principle:

    The non partial discharge fault simulation test device comes with a non partial discharge high voltage, with a partial discharge capacity of less than 3PC under rated voltage of 0-100kV. In the live working mode, the discharge type can be freely selected, and the starting voltage, extinguishing voltage, and discharge intensity of each discharge signal can be controlled. By using traditional partial discharge testing equipment and wireless sensing partial discharge testing equipment, various discharge types such as GIS tip, suspension, air gap, particle, and surface can be tested. Multiple discharges can be generated in combination, providing experiments for technology detection such as pulse current, ultra-high frequency, ultrasonic, high-frequency, SF6 gas analysis, etc.










    You Might Also Like

    • Have Any Questions!

      DON'T HESITATE TO CONTACT US ANY TIME
      Contact us
    • Visit Us

      Building 6, Optics Valley Optical-Mechanical Industrial Park, 84 Gaoxin 5 Road,
      East Lake New Technology Development Zone, Wuhan City, Hubei Province, China

    • Email Us

      qiao@hvtest.cc

    • Call Us

      +86-15871365102