Technical parameters
Working mode | Can be used in stand-alone, parallel, remote control and status monitoring | ||||
Applicable battery pack | 48V | 110V | 220V | 380V | Other electrical test groups can be customized |
Discharge voltage | 38V~60V | 88~132V | 176V~275V | 304V~456V | |
Discharge current | 0~150A | 0~100A | 0~300A | 0~30A | |
Current accuracy | 1% | ||||
Voltage accuracy | 0.5% | ||||
Single cell voltage accuracy | 0.2% | ||||
Cell voltage | 0.500V~16.00V(resolution 1mv) | ||||
Charge and discharge time | 0~99 hours 59 minutes | ||||
Power supply | AC:220V | ||||
cooling method | Forced air-cooled | ||||
Packing | Aluminum alloy trolley case |
Work Environment
Heat dissipation | forced air cooling |
Temperature | working range: -5 ~ 50℃storage temperature: -40 ~ 70℃ |
Humidity | relative to humidity 0 ~ 90% (40±2℃) |
Altitude | rated altitude: 4000m |
Noise | ﹤60dB |
Working Power Supply
Voltage | single-phase three-wire system: 220V AC (- 20% ~ +30%), frequency :45 ~ 65Hz |
Withstand voltage test | input - housing: 2200V DC 1min |
input-output: 2200V DC 1min | |
output - housing: 700V DC 1min | |
Security | meet EN610950 |
Wiring
AC input | Gb socket, suitable for 1 ~ 1.5mm2cable |
DC output | instrument 25mm2 Cable quickconnects plug (red positive black negative) |
Nickname: Battery Discharge Tester; Battery Discharge Analyzer
Main Functions
1. Constant current discharge function, continuously adjustable current, accurate measurement of battery capacity
2. Cell voltage wireless monitoring function, each wireless monitoring module can monitor 12 cells at the same time
3. With Chinese background analysis software, with remote control discharge function
4. The host has a USB interface and 2G large-capacity internal data storage space
5. Using dual CPUs to work together to ensure the safety, reliability and accuracy of the test
Pause and parameter modification can be made during the discharge process, no need to terminate the discharge test