Parameter
Type | - |
Current channel number | Standard six phase |
Voltage channel number | Standard six phase |
AC current output range | 30A / phase or180A (six phase parallel) |
DC current output range | 10A DC /phase |
AC voltage output range | 120V AC /phase |
DC voltage output range | 160V DC / phase |
Nominal parameter
AC current output | ||
Thevirtualvalue of each phase output when six phase current output | 0~30A | |
output precision | 0.1 grade | |
Thevirtualvalue of each phase output when three phase current output | 0~60A | |
Thevirtualvalue of six phase parallel current output | 0~180A | |
The allowedvirtual value when the phase current work long time | 10A | |
The maximum output power of phase current | 450VA
| |
The maximum output power when six phase parallel current output | 1000VA
| |
The allowedworkingtime when six phase parallel current maximum output | 10s | |
Frequency range(fundamental wave) | 0~1000Hz | |
Harmonic order | 0~20
| |
DC current output | ||
Current output | 0~±10A /phase | |
The maximum load volatage output | 0.2 grade | |
ACvoltageoutput | 20V | |
Thevirtualvalue of phasevoltageoutput | 0~120
| |
Voutput precision | 0.1 grade
| |
Thevirtualvalue of line voltageoutput | 0~240V | |
Theoutput power of phase voltage/ line voltage | 80VA / 100VA
| |
Frequency range(fundamental wave) | 0~1000Hz | |
Harmonic order | 0~20 | |
DCvoltageoutput | ||
The output amplitude of phase voltage | 0~±160V | |
output precision | 0.2 grade | |
The output amplitude of line voltage | 0~±320V | |
Theoutput power of phase voltage/ line voltage | 70VA / 140VA | |
Input and output
| ||
8channelsinput
| Free contact | 1~20mA,24V |
Electric potential contacts | “0”:0 ~ +6V; “1”:+11 V~ +250 V | |
4channelsoutput | Electric potential contacts | DC:220 V/0.2 A;AC:220 V/0.5 A
|
Time measurment range
| 0.1ms~ 9999s, measurement accuracy<0.1ms
|
Nickname:six phase relay tester,relay test kit,secondary injection test,Relay Tester
Feature:
Flexible combination of voltage and current output
Six phasevoltage and sixphase current can be output, which has made it is possiable to be any combition, such as theoutput mode of thecombination of conventional four phase current and three-phase current, six phasevoltage mode, six phasecurrent mode and 12 phase output mode. It not only can be compatible with the traditional way of various tests,but alsocan conveniently carry out differential test ofthree-phase transformer.
Operation mode
The device is directly connected with a computer or a desktop computer, which is convenient and efficient and stable performance.
A new hi-filinearpoweramplifier
The output port hasalways insisted onusing themodular linear power amplifierinstead of theswitching power amplifier, which hasthe high fidelity andhigh reliabilityfunction andexcellent performance.High-midfrequency will not be produced to disturbthe test, alsoensurethesmoothing accuracyofwaveformproduced by the whole course ofthe high current to the tiny current is excellent.
High performanceMainframe
Theoutput part adopts DSP control,which hasfast operation, real-time digital signal processing capability, wide bandwidth andhigh resolution D/A conversion control. The output waveform has the features ofhigh precision, small distortion and good linearity.With using a large number of advanced technology and precision components and materials andthe structure of professional design, the device hasthe features ofsmall volume, light weight, full function, easy to carry, boot can work, flow test is very convenient.
Powerful software function
Itcan complete all kinds of high automatic validation work which is large and complex.It canalsoconveniently test and scan protection setting,playback offault, real-time store test data, display vector, online print report and so on. Besides, six-phase current can facilitate the testofthree-phase differential protection.
Independent DC power output
An 110V and 220VadjustableDC power is designed tosupply output.
Complete interface
The device with USB communication portcancommunicate with the computer and other external devices.
Perfect self-protection function
Withreasonable design of the heat dissipation structureandthe reliable and perfect hardware protection measures,it has the power soft start function andthe software of the faultself-diagnosis and the output latch function.